Get Reports
Contact Us
503.641.2222
425.368.4201

Fire Alarm Acceptance Testing – Part IV

Posted on: November 30, 2012

Fire Alarm Acceptance Testing for Central Oregon – Part IV

GENERAL INSTRUCTIONS

  • The following tests require the use of building floor plans showing all initiating devices, notification appliances, fire zones and control relays

  • Proper annunciation (labeling) must be verified for every initiating device

  • Using the input/output matrix, confirm that each activated initiating devise operates the correct notification appliances and any other controlled equipment

  • Record the results of the following tests on acceptable device documentation

  • Every initiating device on the system must be actuated

  • Manual Fire Alarm Boxes (Pull Stations)

– Confirm that each fire alarm box is unobstructed, readily accessible, located in the normal path of egress and that the installed height of each fire alarm box meets applicable requirement

– Activate each manual box by physically operating the device. Opening the fire alarm box with a key is not an acceptable test method

  • Spot Smoke Detectors

– Visually confirm proper application and location of every detector

– Document any misapplication

  • Should not be installed in dead air spaces, or in close proximity to air diffusers
  • Should not be installed on ceilings closer than 4 inches to a wall
  • Sidewall-mounted detectors should be installed between 4 inches and 12 inches from the ceiling
  • Should not be installed closer than 3 feet to an air diffuser or return-air opening
  • Should not be installed near ceiling fans
  • Should not be installed in kitchens, furnace rooms, incinerator rooms, above ashtrays in elevator lobbies or in location where “non-hostile: smoke can normally be expected

– Confirm that there is a smoke detector installed within 21 feet of the FACP, if the FACP area is not continuously occupied

– Activate every spot-type smoke detector with the SOLO test tool or other approved test device (Note: Using the magnetic switch on a detector is not an acceptable test method)

– If detector sensitivity testing is a project requirement, use the smoke detector sensitivity test tool

See NFPA 72 and/or detector white papers for other detector application guidelines

  • Duct Smoke Detectors

– Confirm proper application and location of every duct detector. (For additional information concerning detector placement, refer to NFPA 72)

– Initiate an alarm condition at each duct detector by introducing smoke into the detector (The use of the remote-test switch for an acceptance test is not acceptable. See installation instruction that come with the device for further details on methods for testing duct detectors)

Note: Duct detectors supplied by others, such as the mechanical contractor, are to be tested by the supplier

  • Rate-Of-Rise Heat Detectors

– Activate every rate-of-rise heat detector using the SOLO rate-of-rise test toold or other approved method (Care should be taken to avoid damaging or destroying detectors during testing)

Need Service or Have a Question?
Let’s Talk
Let’s Talk

Get in touch with our experienced team today.

“June 7, 2019 Hello Tracy, I wanted to reach out and thank you for your team’s hard work during the installation of our new fire panel, guest room horns and strobes.  We appreciate your team’s willingness to work alongside our renovation crew to minimize the interruption to our...”

- Kim Saunderson, General Manager Residence Inn, Redmond, WA

“I’ve been working with the Performance Systems Integration team for more than a decade and they have became individually and collectively one of my most valued resources I have. The knowledge base and technical/troubleshooting ability has made them indispensable for all TIs, maintenance and life cycle replacement forecasting. ...”

- Neal McNeal, Chief Engineer ATT, Redmond Town Center Campus/ Willows Technical Center Campus
Affiliates & Certifications