Fire alarm control panel
·
A fire alarm control
panel (FACP), or fire alarm control unit (FACU), is an
electric panel that is the controlling component of a fire
alarm system. The panel receives information from
environmental sensors designed to detect changes associated with
fire, monitors their operational integrity and provides for
automatic control of equipment, and transmission of information
necessary to prepare the facility for fire based on a predetermined
sequence. The panel may also supply electrical energy to operate any
associated sensor, control, transmitter, or relay.
·
There are three basic
types of panels: coded panels, conventional panels, and addressable
panels.
·
Coded panels were the
earliest type of central fire alarm control, and were made from the
1950s to the late 1970s. A coded panel is similar in many ways to a
modern conventional panel (described below), except each zone was
connected to its own code wheel (Ex: An alarm in zone 1 would sound
code 1-2-4 [through the bells or horns in the building], while zone
2 would sound 1-2-5), which, depending on the way the panel was set
up, would either do sets of four rounds of code until the initiating
pull station was reset (similar to a coded pull station)
or run continuously until the panel itself was reset. Large panels
could take up an entire wall in a mechanical room, with dozens of
code wheels. Lists of codes had to be maintained, sometimes with
copies being posted above certain pull stations (this setup is
commonly seen in older wings of hospitals). Smaller panels could be
set up in one of two ways. Most of the time, the panel would only
have one zone, and therefore, only one code. Common one-zone codes
were 4-4-0 and 17-0-0 (which is similar to the 120 bpm March Time
setting found on modern panels). Alternatively, the panel could be
made with no code wheels, using only what was called the gong relay.
In large systems, this was primarily used to accommodate existing
coded pull stations. However, it could also be used as its own zone,
with the connected horns or bells sounding continuously instead of
in a particular code. These panels are not very common today, but
can sometimes be found in older buildings such as those on college
campuses or hospitals.
·
A conventional system
employs one or more initiating circuits, connected to sensors
(initiating devices) wired in parallel. These sensors are devised to
decrease the circuits resistance when the environmental influence on
any sensor exceeds a predetermined threshold. In a conventional
system the information density is limited to the number of such
circuits used.
·
An addressable panel is
a more modern type of panel, and has greater flexibility than a
conventional panel. An addressable panel has a number of loops,
where a number of devices are able to be connected, each with its
own address. There is no standard protocol as such, and thus a
number of proprietary solutions exist. Loop devices have
traditionally been able to have 99 or 100 devices connected, but
more recent protocols allow many more. This is usually overcome by
having multiple loops on one system.
·
A fire alarm control
panel is required under the building code for a
majority of new commercial building construction in most countries
Conventional panels
Conventional panels have
been around ever since electronics became small enough to make them
viable. They are no longer used frequently in large buildings, but
are still used on smaller sites such as small schools or apartments.
Conventional panels usually have a small number
of circuits, each circuit covering a zone within the building. A
small map of the building is often placed near the main entrance
with the defined zones drawn up, and LEDs indicating whether a
particular circuit/zone has been activated. Another common method is
to have the different zones listed in a column, with an LED to the
left of each zone name.
The main drawback with conventional panels is
that one cannot tell which device has been activated within a
circuit. The fire may be in one small room, but as far as emergency
responders can tell, a fire could exist anywhere within a zone. The
same applies to coded panels, which nowadays are no longer made, but
can be found in old systems. These, if the decision is made to keep
them, are "grandfathered" in under NFPA regulations.
Addressable panels
Addressable panels are usually
much more advanced than their conventional counterparts, with a
higher degree of programming flexibility and single point detection.
Notable examples include the EST 3, the Faraday MPC-2000 and the
Simplex 4100U. Addressable fire alarm panels were introduced by many
manufacturers during the microcontroller boom in the mid 1980s.
Initiating Device Loops
Panels usually have a
number of loops within the range of two to 20 loops. At the present
time, four or six loop panels are the most common.
Each loop can have a number of devices connected
to it. Each device has its own address, and so the panel knows the
state of each individual device connected to it. Common addressable
input (initiating) devices include
- Smoke detectors
- Manual call points or
Manual pull stations
- Responders
- Fire sprinkler system
inputs
- Switches
- Flow control
- Pressure
- Isolate
- Standard switches
- Flow control
Addressable output devices are known as relays
and include
- (Warning System/Bell)
Relays
- Door Holder Relays
- Auxiliary (Control
Function) Relays
Relays are used to control a variety of functions
such as
- Switching fans on or off
- Closing/opening doors
- Activating Fire
suppression systems
- Activating notification
appliances
- Shutting down industrial
equipment
Since their
inception, loops have generally been able to handle 99 devices. More
recently however, new protocols have been designed that allow 256
devices on each loop.
Mapping
Also known as "Cause and
Effect" or "Programming", mapping is the process of activating
outputs depending on which inputs have been activated.
Traditionally, when an input device is activated, a certain output
device (or relay) is activated. As time has progressed, more and
more advanced techniques have become available, often with large
variations in style between different companies.
In an EST Panel
mapping has another meaning. Each intelligent device on the
initiating device loop has its own microprocessor. Each device is
electronically addressed and ‘mapped’ by the systems CPU giving its
exact location on the system relevant to it neighboring devices.
This unique system function provides an exact system schematic
diagram of how each initiating device loop is wired making it
invaluable for troubleshooting.
Zones
Zones are usually made by
dividing a building, or area into different sections, and placing
each device in the building in a different zone.
Groups
Groups are used to group two or
more relays. They are used to shorten programming time by allowing
several detectors to link to any particular group which then maps to
a group of relays.
Boolean logic
This is the part of a fire panel
that has the largest variation between different panels. It allows a
panel to be programmed to implement fairly complex inputs. For
instance, a panel could be programmed to notify the fire department
only if more than one device has activated. It can also be used for
staged evacuation procedures in conjunction with
timers.
Networking
The principle of networking
involves connecting several panels together to form a system. Inputs
on one panel may activate outputs on another, for example, or the
network may allow monitoring of many systems. Networking is often
used in situations where one panel is not large enough, or in
multiple-building situations.
Although quasi-standards exist that allow panels
from different manufacturers to be networked with each other, they
are not in favor with a lot of companies (so they are not de-facto
at all). One of the most common of these is named
BACnet
which is used for various types of industrial networks.
More recently, some panels are being networked
with standard Ethernet, but this is not yet very common. Most
organizations choose to create their own proprietary protocol, which
has the added benefit of allowing them to do anything they like,
allowing the technology to progress further. This has the serious
downside, however, of hampering interoperability between
manufacturers.
Networking may be
used to allow a number of different panels to be monitored by one
graphical monitoring system.
Monitoring
In nearly every state in
the USA, the International Building Code requires fire alarm and
sprinkler systems to be monitored by an approved supervising
station.
A fire alarm system consists of a computer-based
control connected to a central station. The majority of fire alarm
systems installed in the USA are monitored by a UL listed or FM
Global approved supervising station.
These systems will generally have a top level map
of the entire site, with various building levels displayed. The user
(most likely a security guard) can progress through the different
stages. From top level site → building plan → floor plan → zone
plan, or however else the building's security system is organized.
A lot of these
systems have touch screens, but most users tend to prefer a mouse
(and a normal monitor), as it is quite easy for a touch screen to
become misaligned and for mistakes to be made. With the advent of
the optical mouse, this is now a very viable option.
System functions
There are many functions on a
fire alarm panel. Some of these are:
System reset
This resets the panel after an
alarm condition. All initiating devices are reset, and the panel is
cleared of any alarm conditions. If an initiating device is still in
alarm after the system is reset, such as a smoke detector continuing
to sense smoke, or a manual pull station still in an activated
position, another alarm will be initiated. A system reset is often
required to clear supervisory conditions. A system reset does not
usually clear trouble conditions. Most trouble conditions will clear
automatically when conditions are returned to normal.
Acknowledge
This function, also abbreviated
to "ACK", is used to acknowledge an abnormal situation such as an
alarm, trouble or supervisory. The acknowledge function tells the
panel that building personnel or emergency responders are aware of
the alarm, trouble, or supervisory condition. Acknowledging the
alarm or trouble condition also normally silences the panel's own
sounder, but does not silence any alarms.
Drill
Also known as "manual evacuation"
or "evacuate". On panels that have this function, the drill function
activates the system's notification appliances, often for purposes
of conducting a fire drill. Using the drill function, an alarm is
normally not transmitted to the fire department or monitoring
center. However, building personnel often notify these agencies in
advance in case an alarm is inadvertently transmitted.
Walk test
Will allow the functional testing
of the systems initiation and notification devices without the
assistance of additional people at the control panel itself.
Alarm silence
Also known as "audible silence".
Depending on the configuration of the alarm system, this function
will either silence the system's notification appliances completely,
or will silence only the audible alarm, with strobe lights
continuing to flash. Audible silence allows for easier communication
amongst emergency responders while responding to an alarm. This can
also be used during construction as a means of a preliminary test,
before the final full test.
Lamp test
Also known as "flash test". This
button is known to have become obsolete, but is still used on many
panels. This function is used to check the condition of the LEDs
themselves. A "Lamp Test" button is required by code on multi-zone
panels installed in Canada.
Alarm circuit supervision
Various forms of alarm
circuit supervision have been used to indicate trouble with an alarm
circuit. Possible alarm circuit faults on a two wire circuit include
one of the conductors being shorted to ground, open circuit
(conductor continuity break), or a short circuit between the
conductors. Also the circuits could be tampered with by having an
external AC or DC voltage applied with various duty cycles or
waveforms. There are a number of US patents that address this issue
and some have been implemented in available system products. One of
the first to address this issue was Patent No. 3,588,890 "Resistance
Sensing Supervisory System" issued on June 28th 1971 and assigned to
General Motors Corporation. General Motors used this supervision on
all circuits installed in GM plants starting in 1970
[1]. An improvement to this basic "Resistance Sensing
Supervisory System" can be obtained by providing a pulsed or time
dependent variable voltage applied to the alarm circuit and is
addressed in US patent numbers 4,030,095 and 4,716,401.
Panel alerting
Many panels today have the
capability of alerting building personnel of a situation which can
arise into a potentially serious problem. Fire alarm panels indicate
an abnormal condition is via a solid or flashing LED. Some panels
also contain a small sounder, used in conjunction with the visual
alert. A number of indicators are shown below. Note that not all
fire alarm panels have all of these indicators.
Alarm
Also known as "Fire". This
indicator is lit when an alarm condition exists in the system,
initiated by smoke detectors, heat detectors, sprinkler flow
switches, manual pull stations, manual call points, or otherwise.
Along with the indicator on the panel, notification appliances, such
as horns and strobes, are also activated, signaling a need to
evacuate to building occupants. In an alarm condition, the fire
alarm panel indicates where the alarm originated. The alarm panel
can be reset once the device which initiated the alarm is reset,
such as returning the handle of a manual pull station to its normal
position.
Audible silence
The Audible Silence indicator is
used in conjunction with the "Alarm" indicator. It indicates that
the fire alarm panel is still in an alarm condition, but that
notification appliances have been silenced. While the alarm is
silenced, other functions in an alarm condition continue to operate,
such as emergency service for elevators, stairway pressurization,
and ventilation functions. A new alarm initiation while the alarm is
silenced will take the panel out of Audible Silence and reactivate
the notification appliances.
Drill
On panels containing this
function, the "Drill" indicator shows that the alarm condition was
activated from the fire alarm panel, often in order to conduct a
fire drill. When an alarm is initiated for a drill, the fire
department or monitoring company is usually not notified
automatically. However, building personnel preparing to conduct a
fire drill often will provide advance notice of a drill to the fire
department and monitoring center in case an alarm is unintentionally
transmitted.
Trouble/fault
Also known as "Defect". When held
steady or flashing, it means that a trouble condition exists on the
panel. Trouble conditions are often activated by a contaminated
smoke detector or an electrical problem within the system. Trouble
conditions are also activated by a zone being disabled (disconnected
from the system), a circuit being disabled, low power on the backup
battery, the disabling of a notification appliance, the ground
faults, or short or open circuits. Usually the alarm panel's sounder
will activate if a trouble condition exists, though older systems
would sometimes activate a bell or other audible signal connected to
the panel. In a trouble condition, the panel displays the zone or
devices causing the condition. The "Trouble" indicator goes out
automatically when the situation causing the trouble condition is
rectified and some panels have more specific indicators such as
'Trouble-PSU' which shows when the panel itself is compromised and
'Trouble-Bell' which shows that the sounders are not functioning
correctly.
Supervisory
This signal indicates that a
portion of the building's fire protection system has been disabled
(such as a fire sprinkler control valve being closed and,
consequentially, a sprinkler tamper switch being activated), or,
less frequently, that a lower priority initiating device has been
triggered (such as a duct smoke detector). The "Supervisory"
indicator may go out automatically when the condition has cleared,
but usually requires a "Reset" to clear.
AC power
Also known as "Normal". When this
indicator is lit, power is being provided to the system from the
building's electrical system, and not from the backup battery. When
an AC power condition changes, the Trouble indicator comes on and
the AC power indicator goes off and the screen alerts building
personnel of a power failure. If the AC power indicator is lit
without any other indicators also lit, then the system is in a
normal condition. If no LEDs are lit, there is no power source
feeding the panel.
DC power
This is used to tell the
operator that DC power (batteries) are being charged or used. While
using DC power, the system remains in a trouble condition.